Preface to the Fourth Edition |
|
xxi | |
Preface to the Third Edition |
|
xxiii | |
Preface to the Second Edition |
|
xxv | |
Preface to the First Edition |
|
xxvii | |
Author |
|
xxix | |
Chapter 1 Introduction and General Philosophies |
|
1 | (36) |
|
1.1 Introduction and Definitions |
|
|
|
1.2 Typical Protective Relays and Relay Systems |
|
|
5 | (3) |
|
1.3 Typical Power Circuit Breakers |
|
|
8 | (3) |
|
1.4 Nomenclature and Device Numbers |
|
|
11 | (5) |
|
1.5 Typical Relay and Circuit Breaker Connections |
|
|
16 | (1) |
|
1.6 Basic Objectives of System Protection |
|
|
17 | (5) |
|
|
19 | (1) |
|
|
20 | (1) |
|
|
20 | (1) |
|
|
21 | (1) |
|
|
21 | (1) |
|
|
22 | (1) |
|
1.7 Factors Affecting the Protection System |
|
|
22 | (1) |
|
|
22 | (1) |
|
|
22 | (1) |
|
1.7.3 Location of Disconnecting and Input Devices |
|
|
23 | (1) |
|
1.7.4 Available Fault Indicators |
|
|
23 | (1) |
|
1.8 Classification of Relays |
|
|
23 | (2) |
|
|
23 | (1) |
|
|
24 | (1) |
|
1.8.3 Reclosing, Synchronism Check, and Synchronizing Relays |
|
|
24 | (1) |
|
|
24 | (1) |
|
|
24 | (1) |
|
1.8.6 Other Relay Classifications |
|
|
24 | (1) |
|
1.9 Protective Relay Performance |
|
|
25 | (1) |
|
|
25 | (1) |
|
1.9.2 Incorrect Operation |
|
|
25 | (1) |
|
|
26 | (1) |
|
1.9.4 Tracking Relay Performance |
|
|
26 | (1) |
|
1.10 Principles of Relay Application |
|
|
26 | (2) |
|
1.11 Information for Application |
|
|
28 | (2) |
|
1.11.1 System Configuration |
|
|
28 | (1) |
|
1.11.2 Impedance and Connection of the Power Equipment, System Frequency, System Voltage, and System Phase Sequence |
|
|
29 | (1) |
|
1.11.3 Existing Protection and Problems |
|
|
29 | (1) |
|
1.11.4 Operating Procedures and Practices |
|
|
29 | (1) |
|
1.11.5 Importance of the System Equipment Being Protected |
|
|
29 | (1) |
|
1.11.6 System Fault Study |
|
|
29 | (1) |
|
1.11.7 Maximum Loads and System Swing Limits |
|
|
30 | (1) |
|
1.11.8 Current and Voltage Transformer Locations, Connections, and Ratios |
|
|
30 | (1) |
|
|
30 | (1) |
|
1.12 Structural Changes within the Electric Power Industry |
|
|
30 | (2) |
|
1.13 Reliability and Protection Standards |
|
|
32 | (2) |
|
1.13.1 Regulatory Agencies |
|
|
33 | (1) |
|
|
34 | (3) |
Chapter 2 Fundamental Units: Per-Unit and Percent Values |
|
37 | (14) |
|
|
37 | (1) |
|
2.2 Per-Unit and Percent Definitions |
|
|
37 | (1) |
|
2.3 Advantages of Per Unit and Percent |
|
|
38 | (1) |
|
2.4 General Relations between Circuit Quantities |
|
|
38 | (2) |
|
|
40 | (1) |
|
2.6 Per-Unit and Percent Impedance Relations |
|
|
41 | (1) |
|
2.7 Per-Unit and Percent Impedances of Transformer Units |
|
|
42 | (3) |
|
2.7.1 Transformer Bank Example |
|
|
44 | (1) |
|
2.8 Per-Unit and Percent Impedances of Generators |
|
|
45 | (1) |
|
2.9 Per-Unit and Percent Impedances of Overhead Lines |
|
|
46 | (1) |
|
2.10 Changing Per-Unit (Percent) Quantities to Different Bases |
|
|
46 | (3) |
|
2.10.1 Example: Base Conversion with Equation 2.34 |
|
|
47 | (1) |
|
2.10.2 Example: Base Conversion Requiring Equation 2.33 |
|
|
48 | (1) |
|
|
49 | (2) |
Chapter 3 Phasors and Polarity |
|
51 | (20) |
|
|
51 | (1) |
|
|
51 | (5) |
|
3.2.1 Phasor Representation |
|
|
51 | (2) |
|
3.2.2 Phasor Diagrams for Sinusoidal Quantities |
|
|
53 | (1) |
|
|
53 | (1) |
|
3.2.4 Phasor Diagrams Require a Circuit Diagram |
|
|
54 | (1) |
|
3.2.5 Nomenclature for Current and Voltage |
|
|
54 | (2) |
|
|
54 | (1) |
|
|
55 | (1) |
|
|
56 | (1) |
|
3.3 Circuit and Phasor Diagrams for a Balanced Three-Phase Power System |
|
|
56 | (2) |
|
3.4 Phasor and Phase Rotation |
|
|
58 | (1) |
|
|
58 | (5) |
|
3.5.1 Transformer Polarity |
|
|
58 | (3) |
|
|
61 | (2) |
|
3.6 Application of Polarity for Phase-Fault Directional Sensing |
|
|
63 | (3) |
|
3.6.1 90°-60° Connection for Phase-Fault Protection |
|
|
64 | (2) |
|
3.7 Directional Sensing for Ground Faults: Voltage Polarization |
|
|
66 | (1) |
|
3.8 Directional Sensing for Ground Faults: Current Polarization |
|
|
67 | (1) |
|
3.9 Other Directional-Sensing Connections |
|
|
68 | (1) |
|
3.10 Application Aspects of Directional Relaying |
|
|
69 | (1) |
|
|
70 | (1) |
Chapter 4 Symmetrical Components: A Review |
|
71 | (74) |
|
4.1 Introduction and Background |
|
|
71 | (1) |
|
4.2 Positive-Sequence Set |
|
|
72 | (1) |
|
4.3 Nomenclature Convenience |
|
|
73 | (1) |
|
4.4 Negative-Sequence Set |
|
|
73 | (1) |
|
|
74 | (1) |
|
|
74 | (1) |
|
4.7 Sequence Independence |
|
|
75 | (1) |
|
4.8 Positive-Sequence Sources |
|
|
76 | (2) |
|
|
78 | (7) |
|
4.9.1 Positive-Sequence Network |
|
|
78 | (2) |
|
4.9.2 Negative-Sequence Network |
|
|
80 | (2) |
|
4.9.3 Zero-Sequence Network |
|
|
82 | (2) |
|
4.9.4 Sequence Network Reduction |
|
|
84 | (1) |
|
4.10 Shunt Unbalance Sequence Network Interconnections |
|
|
85 | (6) |
|
|
85 | (1) |
|
4.10.2 Substation and Tower-Footing Impedance |
|
|
86 | (1) |
|
4.10.3 Sequence Interconnections for Three-Phase Faults |
|
|
86 | (1) |
|
4.10.4 Sequence Interconnections for Single-Phase-to-Ground Faults |
|
|
87 | (1) |
|
4.10.5 Sequence Interconnections for Phase-to-Phase Faults |
|
|
88 | (1) |
|
4.10.6 Sequence Interconnections for Double-Phase-to-Ground Faults |
|
|
89 | (1) |
|
4.10.7 Other Sequence Interconnections for Shunt System Conditions |
|
|
90 | (1) |
|
4.11 Example: Fault Calculations on a Typical System Shown in Figure 4.16 |
|
|
91 | (4) |
|
4.11.1 Three-Phase Fault at Bus G |
|
|
93 | (1) |
|
4.11.2 Single-Phase-to-Ground Fault at Bus G |
|
|
94 | (1) |
|
4.12 Example: Fault Calculation for Autotransformers |
|
|
95 | (4) |
|
4.12.1 Single-Phase-to-Ground Fault at H Calculation |
|
|
97 | (2) |
|
4.13 Example: Open-Phase Conductor |
|
|
99 | (1) |
|
4.14 Example: Open-Phase Falling to Ground on One Side |
|
|
99 | (3) |
|
4.15 Series and Simultaneous Unbalances |
|
|
102 | (1) |
|
|
103 | (8) |
|
4.16.1 Voltage and Current Phasors for Shunt Faults |
|
|
103 | (1) |
|
4.16.2 System Voltage Profiles during Faults |
|
|
104 | (3) |
|
4.16.3 Unbalanced Currents in the Unfaulted Phases for Phase-to-Ground Faults in Loop Systems |
|
|
107 | (1) |
|
4.16.4 Voltage and Current Fault Phasors for All Combinations of the Different Faults |
|
|
108 | (3) |
|
|
111 | (1) |
|
|
112 | (1) |
|
Appendix 4.1 Short-Circuit MVA and Equivalent Impedance |
|
|
113 | (2) |
|
Appendix 4.2 Impedance and Sequence Connections for Transformer Banks |
|
|
115 | (7) |
|
Appendix 4.3 Sequence Phase Shifts through Wye–Delta Transformer Banks |
|
|
122 | (3) |
|
Appendix 4.4 Impedance of Overhead Lines |
|
|
125 | (16) |
|
Appendix 4.5 Zero-Sequence Impedance of Transformers |
|
|
141 | (4) |
Chapter 5 Relay Input Sources |
|
145 | (28) |
|
|
145 | (1) |
|
5.2 Equivalent Circuits of Current and Voltage Transformers |
|
|
145 | (5) |
|
5.3 CTs for Protection Applications |
|
|
150 | (1) |
|
5.4 CT Performance on a Symmetrical AC Component |
|
|
150 | (5) |
|
5.4.1 Performance by Classic Analysis |
|
|
151 | (1) |
|
5.4.2 Performance by CT Characteristic Curves |
|
|
151 | (1) |
|
5.4.3 Performance by ANSI/IEEE Standard Accuracy Classes |
|
|
151 | (4) |
|
5.4.4 IEC Standard Accuracy Classes |
|
|
155 | (1) |
|
5.5 Secondary Burdens during Faults |
|
|
155 | (2) |
|
5.6 CT Selection and Performance Evaluation for Phase Faults |
|
|
157 | (4) |
|
5.6.1 CT Ratio Selection for Phase-Connected Equipment |
|
|
157 | (1) |
|
5.6.2 Select the Relay Tap for the Phase–Overcurrent Relays |
|
|
157 | (1) |
|
5.6.3 Determine the Total Connected Secondary Load (Burden) in Ohms |
|
|
158 | (1) |
|
5.6.4 Determine the CT Performance Using the ANSI/IEEE Standard |
|
|
158 | (7) |
|
5.6.4.1 When Using a Class T CT |
|
|
158 | (1) |
|
5.6.4.2 When Using a Class C CT and Performance by the ANSI/IEEE Standard |
|
|
159 | (1) |
|
5.6.4.3 When Using a Class C CT and Performance with the CT Excitation Curves |
|
|
160 | (1) |
|
5.7 Performance Evaluation for Ground Relays |
|
|
161 | (1) |
|
5.8 Effect of Unenergized CTs on Performance |
|
|
161 | (2) |
|
5.9 Flux Summation Current Transformer |
|
|
163 | (1) |
|
5.10 Current Transformer Performance on the DC Component |
|
|
164 | (1) |
|
5.11 Summary: Current Transformer Performance Evaluation |
|
|
165 | (2) |
|
5.11.1 Saturation on Symmetrical AC Current Input Resulting from the CT Characteristics and the Secondary Load |
|
|
165 | (1) |
|
5.11.2 Saturation by the DC Offset of the Primary AC Current |
|
|
166 | (1) |
|
5.12 Current Transformer Residual Flux and Subsidence Transients |
|
|
167 | (1) |
|
5.13 Auxiliary Current Transformers in CT Secondary Circuits |
|
|
168 | (1) |
|
5.14 Voltage Transformers for Protective Applications |
|
|
169 | (1) |
|
|
170 | (2) |
|
|
172 | (1) |
Chapter 6 Protection Fundamentals and Basic Design Principles |
|
173 | (26) |
|
|
173 | (1) |
|
6.2 Differential Principle |
|
|
173 | (3) |
|
6.3 Overcurrent–Distance Protection and the Basic Protection Problem |
|
|
176 | (2) |
|
|
177 | (1) |
|
6.3.2 Communication Solution |
|
|
178 | (1) |
|
6.4 Backup Protection: Remote versus Local |
|
|
178 | (1) |
|
6.5 Basic Design Principles |
|
|
179 | (17) |
|
6.5.1 Time–Overcurrent Relays |
|
|
179 | (3) |
|
6.5.2 Instantaneous Current–Voltage Relays |
|
|
182 | (2) |
|
6.5.3 Directional-Sensing Power Relays |
|
|
184 | (1) |
|
|
184 | (1) |
|
6.5.5 Phase Distance Relays |
|
|
185 | (1) |
|
6.5.5.1 Balanced Beam Type: Impedance Characteristic |
|
|
185 | (1) |
|
|
186 | (1) |
|
|
186 | (3) |
|
6.5.8 Single-Phase Mho Units |
|
|
189 | (1) |
|
6.5.9 Polyphase Mho Units |
|
|
190 | (2) |
|
6.5.9.1 Three-Phase Fault Units |
|
|
190 | (2) |
|
6.5.9.2 Phase-to-Phase Fault Units |
|
|
192 | (1) |
|
|
192 | (2) |
|
|
194 | (1) |
|
6.6 Ground Distance Relays |
|
|
194 | (2) |
|
6.7 Solid-State Microprocessor Relays |
|
|
196 | (2) |
|
|
198 | (1) |
|
|
198 | (1) |
Chapter 7 System-Grounding Principles |
|
199 | (36) |
|
|
199 | (1) |
|
|
199 | (4) |
|
7.3 Transient Overvoltages |
|
|
203 | (1) |
|
7.4 Grounded-Detection Methods for Ungrounded Systems |
|
|
204 | (4) |
|
7.4.1 Three Voltage Transformers |
|
|
204 | (2) |
|
7.4.2 Single-Voltage Transformers |
|
|
206 | (2) |
|
7.5 High-Impedance Grounding Systems |
|
|
208 | (10) |
|
|
208 | (1) |
|
7.5.2 High-Resistance Grounding |
|
|
209 | (1) |
|
7.5.3 Example: Typical High-Resistance Neutral Grounding |
|
|
210 | (5) |
|
7.5.4 Example: Typical High-Resistance Grounding with Three Distribution Transformers |
|
|
215 | (3) |
|
7.6 System Grounding for Mine or Other Hazardous-Type Applications |
|
|
218 | (1) |
|
7.7 Low-Impedance Grounding |
|
|
218 | (5) |
|
7.7.1 Example: Typical Low-Resistance Neutral Reactor Grounding |
|
|
221 | (1) |
|
7.7.2 Example: Typical Low-Resistance Neutral Resistance Grounding |
|
|
222 | (1) |
|
7.8 Solid (Effective) Grounding |
|
|
223 | (2) |
|
7.8.1 Example: Solid Grounding |
|
|
223 | (2) |
|
7.8.2 Ground Detection on Solid-Grounded Systems |
|
|
225 | (1) |
|
7.9 Ferroresonance in Three-Phase Power Systems |
|
|
225 | (5) |
|
7.9.1 General Summary for Ferroresonance for Distribution Systems |
|
|
229 | (1) |
|
7.9.2 Ferroresonance at High Voltages |
|
|
229 | (1) |
|
|
230 | (1) |
|
7.11 Grounding Summary and Recommendations |
|
|
231 | (2) |
|
|
233 | (2) |
Chapter 8 Generator Protection/Intertie Protection for Distributed Generation |
|
235 | (60) |
|
|
235 | (5) |
|
8.1.1 Historical Perspectives |
|
|
235 | (2) |
|
8.1.2 Bulk Power Generators |
|
|
237 | (1) |
|
8.1.3 Distributed Generators |
|
|
238 | (1) |
|
|
239 | (1) |
|
8.2 Generator Connections and Overview of Typical Protection |
|
|
240 | (2) |
|
8.3 Stator Phase-Fault Protection for All Size Generators |
|
|
242 | (8) |
|
8.3.1 Differential Protection (87) for Small kVA (MVA) Generators |
|
|
242 | (1) |
|
8.3.2 Multi-CT Differential Protection (87) for All Size Generators |
|
|
243 | (3) |
|
8.3.3 High-Impedance Voltage Differential Protection for Generators |
|
|
246 | (1) |
|
8.3.4 Direct-Connected Generator Current Differential Example |
|
|
246 | (1) |
|
8.3.5 Phase Protection for Small Generators That Do Not Use Differentials |
|
|
247 | (1) |
|
8.3.6 Unit Generator Current Differential (87) Example for Phase Protection |
|
|
248 | (2) |
|
8.4 Unit Transformer Phase-Fault Differential Protection (87TG) |
|
|
250 | (1) |
|
8.5 Phase-Fault Backup Protection (51 V) or (21) |
|
|
251 | (1) |
|
8.5.1 Voltage-Controlled or Voltage-Restraint Time-Overcurrent (51 V) Backup Protection |
|
|
251 | (1) |
|
8.5.2 Phase Distance (21) Backup Protection |
|
|
252 | (1) |
|
8.6 Negative-Sequence Current Backup Protection |
|
|
252 | (1) |
|
8.7 Stator Ground-Fault Protection |
|
|
253 | (8) |
|
8.7.1 Ground-Fault Protection for Single Medium or Small Wye-Connected Generators (Type la: See Figures 8.3 and 8.11) |
|
|
253 | (1) |
|
8.7.2 Ground-Fault Protection of Multiple Medium or Small Wye- or Delta-Connected Generators (Type 2: See Figures 8.2 and 8.12) |
|
|
254 | (1) |
|
8.7.3 Ground-Fault Protection for Ungrounded Generators |
|
|
255 | (1) |
|
8.7.4 Ground-Fault Protection for Very Small, Solidly Grounded Generators |
|
|
256 | (1) |
|
8.7.5 Ground-Fault Protection for Unit-Connected Generators Using High-Impedance Neutral Grounding (Type lb: See Figure 8.5) |
|
|
256 | (1) |
|
8.7.6 Added Protection for 100% Generator Ground Protection with High-Resistance Grounding |
|
|
257 | (2) |
|
8.7.7 High-Voltage Ground-Fault Coupling Can Produce V0 in High-Impedance Grounding Systems |
|
|
259 | (2) |
|
8.7.8 Ground-Fault Protection for Multidirect-Connected Generators Using High-Resistance Grounding |
|
|
261 | (1) |
|
8.8 Multiple Generator Units Connected Directly to a Transformer: Grounding and Protection |
|
|
261 | (1) |
|
8.9 Field Ground Protection (64) |
|
|
262 | (1) |
|
8.10 Generator Off-Line Protection |
|
|
262 | (1) |
|
8.11 Reduced or Lost_Excitation Protection (40) |
|
|
262 | (4) |
|
8.11.1 Loss of Excitation Protection with Distance (21) Relays |
|
|
262 | (4) |
|
8.11.2 Loss of Excitation Protection with a Var-Type Relay |
|
|
266 | (1) |
|
8.12 Generator Protection for System Disturbances and Operational Hazards |
|
|
266 | (6) |
|
8.12.1 Loss of Prime Mover: Generator Motoring (32) |
|
|
267 | (1) |
|
8.12.2 Overexcitation: Volts per Hertz Protection (24) |
|
|
267 | (1) |
|
8.12.3 Inadvertent Energization: Nonsynchronized Connection (67) |
|
|
268 | (1) |
|
8.12.4 Breaker Pole Flashover (61) |
|
|
268 | (1) |
|
8.12.5 Thermal Overload (49) |
|
|
269 | (1) |
|
8.12.6 Off-Frequency Operation |
|
|
269 | (1) |
|
|
270 | (1) |
|
8.12.8 Loss of Synchronism: Out-of-Step |
|
|
270 | (1) |
|
8.12.9 Subsynchronous Oscillations |
|
|
271 | (1) |
|
8.13 Loss of Voltage Transformer Signal |
|
|
272 | (1) |
|
8.14 Generator Breaker Failure |
|
|
273 | (1) |
|
8.15 Excitation System Protection and Limiters |
|
|
273 | (3) |
|
|
274 | (1) |
|
8.15.2 Field Overexcitation |
|
|
274 | (1) |
|
8.15.3 Field Underexcitation |
|
|
275 | (1) |
|
8.15.4 Practical Considerations |
|
|
275 | (1) |
|
8.16 Synchronous Condenser Protection |
|
|
276 | (1) |
|
8.17 Generator-Tripping Systems |
|
|
276 | (1) |
|
8.18 Station Auxiliary Service System |
|
|
276 | (1) |
|
8.19 Distributed Generator Intertie Protection |
|
|
277 | (14) |
|
8.19.1 Power Quality Protection |
|
|
278 | (5) |
|
8.19.2 Power System Fault Protection |
|
|
283 | (1) |
|
8.19.3 System Protection for Faults on Distributed Generator Facilities |
|
|
284 | (1) |
|
8.19.4 Other Intertie Protection Considerations |
|
|
285 | (1) |
|
8.19.5 Induction Generators/Static Inverters/Wind Farms |
|
|
285 | (4) |
|
8.19.5.1 Induction Generators |
|
|
285 | (1) |
|
|
286 | (2) |
|
|
288 | (1) |
|
8.19.6 Practical Considerations of Distributed Generation |
|
|
289 | (2) |
|
|
291 | (1) |
|
|
292 | (3) |
Chapter 9 Transformer, Reactor, and Shunt Capacitor Protection |
|
295 | (76) |
|
|
295 | (2) |
|
9.2 Factors Affecting Differential Protection |
|
|
297 | (1) |
|
9.3 False Differential Current |
|
|
298 | (3) |
|
9.3.1 Magnetization Inrush |
|
|
298 | (2) |
|
|
300 | (1) |
|
9.3.3 Current Transformer Saturation |
|
|
301 | (1) |
|
9.4 Transformer Differential Relay Characteristics |
|
|
301 | (2) |
|
9.5 Application and Connection of Transformer Differential Relays |
|
|
303 | (1) |
|
9.6 Example: Differential Protection Connections for a Two-Winding Wye–Delta Transformer Bank |
|
|
304 | (3) |
|
9.6.1 First Step: Phasing |
|
|
304 | (2) |
|
9.6.2 Second Step: CT Ratio and Tap Selections |
|
|
306 | (1) |
|
9.7 Load Tap-Changing Transformers |
|
|
307 | (1) |
|
9.8 Example: Differential Protection Connections for Multiwinding Transformer Bank |
|
|
308 | (3) |
|
9.9 Application of Auxiliaries for Current Balancing |
|
|
311 | (1) |
|
9.10 Paralleling CTs in Differential Circuits |
|
|
311 | (2) |
|
9.11 Special Connections for Transformer Differential Relays |
|
|
313 | (2) |
|
9.12 Differential Protection for Three-Phase Banks of Single-Phase Transformer Units |
|
|
315 | (1) |
|
9.13 Ground (Zero-Sequence) Differential Protection for Transformers |
|
|
316 | (1) |
|
9.14 Equipment for Transfer Trip Systems |
|
|
317 | (1) |
|
|
317 | (1) |
|
9.14.2 Communication Channel |
|
|
318 | (1) |
|
9.14.3 Limited Fault-Interruption Device |
|
|
318 | (1) |
|
9.15 Mechanical Fault Detection for Transformers |
|
|
318 | (1) |
|
|
318 | (1) |
|
|
319 | (1) |
|
9.16 Grounding Transformer Protection |
|
|
319 | (2) |
|
9.17 Ground Differential Protection with Directional Relays |
|
|
321 | (3) |
|
9.18 Protection of Regulating Transformers |
|
|
324 | (1) |
|
9.19 Transformer Overcurrent Protection |
|
|
324 | (4) |
|
9.20 Transformer Overload-through-Fault-Withstand Standards |
|
|
328 | (2) |
|
9.21 Examples: Transformer Overcurrent Protection |
|
|
330 | (9) |
|
9.21.1 Industrial Plant or Similar Facility Served by a 2500 kVA, 12 kV: 480 V Transformer with 5.75% Impedance |
|
|
331 | (4) |
|
9.21.2 Distribution or Similar Facility Served by a 7500 kVA, 115: 12 kV Transformer with7.8% Impedance |
|
|
335 | (2) |
|
9.21.3 Substation Served by a 12/16/20 MVA, 115: 12.5 kV Transformer with 10% Impedance |
|
|
337 | (2) |
|
9.22 Transformer Thermal Protection |
|
|
339 | (1) |
|
9.23 Overvoltage on Transformers |
|
|
339 | (1) |
|
9.24 Summary: Typical Protection for Transformers |
|
|
340 | (5) |
|
9.24.1 Individual Transformer Units |
|
|
340 | (1) |
|
9.24.2 Parallel Transformer Units |
|
|
341 | (3) |
|
9.24.3 Redundancy Requirements for Bulk Power Transformers |
|
|
344 | (1) |
|
|
345 | (2) |
|
|
345 | (1) |
|
9.25.2 General Application of Shunt Reactors |
|
|
346 | (1) |
|
9.25.3 Reactor Protection |
|
|
346 | (1) |
|
|
347 | (1) |
|
9.27 Power System Reactive Requirements |
|
|
347 | (1) |
|
9.28 Shunt Capacitor Applications |
|
|
348 | (1) |
|
9.29 Capacitor Bank Designs |
|
|
349 | (1) |
|
9.30 Distribution Capacitors Bank Protection |
|
|
350 | (1) |
|
9.31 Designs and Limitations of Large Capacitor Banks |
|
|
351 | (3) |
|
9.32 Protection of Large Capacitor Banks |
|
|
354 | (5) |
|
9.33 Series Capacitor Bank Protection |
|
|
359 | (1) |
|
9.34 Capacitor Bank Protection Application Issues |
|
|
360 | (1) |
|
|
361 | (1) |
|
Appendix 9.1 Application of Digital Transformer Differential Relays |
|
|
362 | (9) |
Chapter 10 Bus Protection |
|
371 | (20) |
|
10.1 Introduction: Typical Bus Arrangements |
|
|
371 | (2) |
|
10.2 Single Breaker–Single Bus |
|
|
373 | (1) |
|
10.3 Single Buses Connected with Bus Ties |
|
|
373 | (1) |
|
10.4 Main and Transfer Buses with Single Breakers |
|
|
374 | (3) |
|
10.5 Single Breaker–Double Bus |
|
|
377 | (1) |
|
10.6 Double Breaker–Double Bus |
|
|
378 | (1) |
|
|
378 | (1) |
|
10.8 Breaker-and-Half Bus |
|
|
378 | (1) |
|
10.9 Transformer–Bus Combination |
|
|
379 | (1) |
|
10.10 General Summary of Buses |
|
|
379 | (1) |
|
10.11 Differential Protection for Buses |
|
|
379 | (7) |
|
10.11.1 Multirestraint Current Differential |
|
|
381 | (2) |
|
10.11.2 High-Impedance Voltage Differential |
|
|
383 | (1) |
|
10.11.3 Air-Core Transformer Differential |
|
|
384 | (1) |
|
10.11.4 Moderate High-Impedance Differential |
|
|
385 | (1) |
|
10.12 Other Bus Differential Systems |
|
|
386 | (3) |
|
10.12.1 Time–Overcurrent Differential |
|
|
386 | (1) |
|
10.12.2 Directional Comparison Differential |
|
|
386 | (1) |
|
10.12.3 Partial Differential |
|
|
386 | (2) |
|
10.12.4 Short Time-Delay Scheme: Instantaneous Blocking |
|
|
388 | (1) |
|
|
389 | (1) |
|
|
389 | (1) |
|
10.15 Bus Protection: Practical Considerations |
|
|
389 | (1) |
|
|
390 | (1) |
Chapter 11 Motor Protection |
|
391 | (24) |
|
|
391 | (1) |
|
11.2 Potential Motor Hazards |
|
|
391 | (1) |
|
11.3 Motor Characteristics Involved in Protection |
|
|
392 | (1) |
|
11.4 Induction Motor Equivalent Circuit |
|
|
393 | (2) |
|
11.5 General Motor Protection |
|
|
395 | (1) |
|
11.6 Phase-Fault Protection |
|
|
395 | (2) |
|
11.7 Differential Protection |
|
|
397 | (1) |
|
11.8 Ground-Fault Protection |
|
|
398 | (2) |
|
11.9 Thermal and Locked-Rotor Protection |
|
|
400 | (2) |
|
11.10 Locked-Rotor Protection for Large Motors (21) |
|
|
402 | (1) |
|
11.11 System Unbalance and Motors |
|
|
403 | (5) |
|
11.12 Unbalance and Phase Rotation Protection |
|
|
408 | (1) |
|
11.13 Undervoltage Protection |
|
|
409 | (1) |
|
11.14 Bus Transfer and Reclosing |
|
|
409 | (1) |
|
11.15 Repetitive Starts and Jogging Protection |
|
|
410 | (1) |
|
11.16 Multifunction Microprocessor Motor Protection Units |
|
|
410 | (1) |
|
11.17 Synchronous Motor Protection |
|
|
411 | (1) |
|
11.18 Summary: Typical Protection for Motors |
|
|
411 | (1) |
|
11.19 Practical Considerations of Motor Protection |
|
|
412 | (1) |
|
|
413 | (2) |
Chapter 12 Line Protection |
|
415 | (58) |
|
12.1 Classifications of Lines and Feeders |
|
|
415 | (3) |
|
12.2 Line Classifications for Protection |
|
|
418 | (2) |
|
12.2.1 Distribution Lines |
|
|
419 | (1) |
|
12.2.2 Transmission and Subtransmission Lines |
|
|
420 | (1) |
|
12.3 Techniques and Equipment for Line Protection |
|
|
420 | (4) |
|
|
421 | (1) |
|
12.3.2 Automatic Circuit Reclosers |
|
|
421 | (1) |
|
|
422 | (1) |
|
12.3.4 Coordinating Time Interval |
|
|
422 | (2) |
|
12.4 Coordination Fundamentals and General Setting Criteria |
|
|
424 | (2) |
|
12.4.1 Phase Time–Overcurrent Relay Setting |
|
|
425 | (1) |
|
12.4.2 Ground Time–Overcurrent Relay Setting |
|
|
425 | (1) |
|
12.4.3 Phase and Ground Instantaneous Overcurrent Relay Setting |
|
|
426 | (1) |
|
12.5 Distribution Feeder, Radial Line Protection, and Coordination |
|
|
426 | (3) |
|
12.6 Example: Coordination for a Typical Distribution Feeder |
|
|
429 | (4) |
|
12.6.1 Practical Distribution Coordination Considerations |
|
|
432 | (1) |
|
12.7 Distributed Generators and Other Sources Connected to Distribution Lines |
|
|
433 | (1) |
|
12.8 Example: Coordination for a Loop System |
|
|
434 | (6) |
|
12.9 Instantaneous Trip Application for a Loop System |
|
|
440 | (1) |
|
12.10 Short-Line Applications |
|
|
441 | (1) |
|
12.11 Network and Spot Network Systems |
|
|
442 | (1) |
|
12.12 Distance Protection for Phase Faults |
|
|
442 | (3) |
|
12.13 Distance Relay Applications for Tapped and Multiterminal Lines |
|
|
445 | (2) |
|
12.14 Voltage Sources for Distance Relays |
|
|
447 | (1) |
|
12.15 Distance Relay Applications in Systems Protected by Inverse-Time–Overcurrent Relays |
|
|
448 | (1) |
|
12.16 Ground-Fault Protection for Lines |
|
|
448 | (1) |
|
12.17 Distance Protection for Ground Faults and Direction Overcurrent Comparisons |
|
|
448 | (2) |
|
12.18 Fault Resistance and Relaying |
|
|
450 | (2) |
|
12.19 Directional Sensing for Ground–Overcurrent Relays |
|
|
452 | (1) |
|
12.20 Polarizing Problems with Autotransformers |
|
|
453 | (3) |
|
12.21 Voltage Polarization Limitations |
|
|
456 | (1) |
|
12.22 Dual Polarization for Ground Relaying |
|
|
456 | (1) |
|
12.23 Ground Directional Sensing with Negative Sequence |
|
|
457 | (1) |
|
12.24 Mutual Coupling and Ground Relaying |
|
|
457 | (6) |
|
12.25 Ground Distance Relaying with Mutual Induction |
|
|
463 | (1) |
|
12.26 Long EHV Series-Compensated Line Protection |
|
|
464 | (1) |
|
12.27 Backup: Remote, Local, and Breaker Failure |
|
|
465 | (4) |
|
12.28 Summary: Typical Protection for Lines |
|
|
469 | (1) |
|
12.29 Practical Considerations of Line Protection |
|
|
470 | (1) |
|
|
470 | (3) |
Chapter 13 Pilot Protection |
|
473 | (46) |
|
|
473 | (1) |
|
13.2 Pilot System Classifications |
|
|
473 | (1) |
|
13.3 Protection Channel Classifications |
|
|
474 | (1) |
|
13.4 Directional Comparison Blocking Pilot Systems |
|
|
475 | (2) |
|
13.5 Directional Comparison Unblocking Pilot System |
|
|
477 | (2) |
|
13.5.1 Normal-Operating Condition (No Faults) |
|
|
478 | (1) |
|
|
479 | (1) |
|
13.5.3 External Fault on Bus G or in the System to the Left |
|
|
479 | (1) |
|
13.5.4 Internal Faults in the Protected Zone |
|
|
479 | (1) |
|
13.6 Directional Comparison Overreaching Transfer Trip Pilot Systems |
|
|
479 | (2) |
|
13.6.1 External Fault on Bus G or in the System to the Left |
|
|
481 | (1) |
|
13.6.2 Internal Faults in the Protected Zone |
|
|
481 | (1) |
|
13.7 Directional Comparison Underreaching Transfer Trip Pilot Systems |
|
|
481 | (2) |
|
|
483 | (1) |
|
13.8 Phase Comparison: Pilot Wire Relaying (Wire Line Channels) |
|
|
483 | (3) |
|
13.9 Phase Comparison: Audio Tone or Fiber-Optic Channels |
|
|
486 | (2) |
|
13.9.1 External Fault on Bus H or in the System to the Right |
|
|
486 | (1) |
|
13.9.2 Internal Faults in the Protected Zone |
|
|
487 | (1) |
|
13.10 Segregated Phase Comparison Pilot Systems |
|
|
488 | (1) |
|
13.11 Single-Pole–Selective-Pole Pilot Systems |
|
|
488 | (1) |
|
13.12 Directional Wave Comparison Systems |
|
|
489 | (1) |
|
13.13 Digital Current Differential |
|
|
490 | (1) |
|
13.14 Pilot Scheme Enhancements |
|
|
490 | (1) |
|
13.14.1 Transient Blocking |
|
|
490 | (1) |
|
13.14.2 Weak Infeed Logic |
|
|
491 | (1) |
|
13.14.3 Breaker Open Keying |
|
|
491 | (1) |
|
13.15 Transfer Trip Systems |
|
|
491 | (1) |
|
13.16 Communication Channels for Protection |
|
|
492 | (4) |
|
13.16.1 Power-Line Carrier: On–Off or Frequency Shift |
|
|
492 | (2) |
|
13.16.2 Pilot Wires: Audio-Tone Transmission |
|
|
494 | (1) |
|
13.16.3 Pilot Wires: 50 or 60 Hz Transmission |
|
|
494 | (1) |
|
|
494 | (2) |
|
13.17 Digital Line Current Differential Systems |
|
|
496 | (12) |
|
13.17.1 Characteristics of Line Differential Schemes |
|
|
496 | (1) |
|
13.17.2 Line Differential Issues |
|
|
497 | (5) |
|
13.17.2.1 Current Sample Alignment |
|
|
498 | (1) |
|
13.17.2.2 Current Transformer Saturation |
|
|
499 | (1) |
|
13.17.2.3 Line Charging Current |
|
|
500 | (1) |
|
|
500 | (2) |
|
13.17.3 Line Differential Design Enhancements |
|
|
502 | (6) |
|
13.17.3.1 Sensitivity Enhancement |
|
|
502 | (1) |
|
13.17.3.2 Maintaining Adequate Data Alignment |
|
|
503 | (1) |
|
13.17.3.3 Mitigating Impacts of Current Transformer Saturation |
|
|
503 | (1) |
|
13.17.3.4 Accounting for Line Charging Current |
|
|
504 | (1) |
|
13.17.3.5 Current-Ratio Differential Concept |
|
|
504 | (4) |
|
13.17.4 Line Differential Application |
|
|
508 | (1) |
|
13.18 Pilot Relaying: Operating Experiences |
|
|
508 | (2) |
|
|
510 | (2) |
|
|
512 | (1) |
|
Appendix 13.1 Protection of Wire Line Pilot Circuits |
|
|
513 | (6) |
Chapter 14 Stability, Reclosing, Load Shedding, and Trip Circuit Design |
|
519 | (34) |
|
|
519 | (1) |
|
14.2 Electric Power and Power Transmission |
|
|
519 | (2) |
|
14.3 Steady-State Operation and Stability |
|
|
521 | (1) |
|
14.4 Transient Operation and Stability |
|
|
521 | (3) |
|
14.5 System Swings and Protection |
|
|
524 | (5) |
|
14.6 Out-of-Step Detection by Distance Relays |
|
|
529 | (2) |
|
14.7 Automatic Line Reclosing |
|
|
531 | (1) |
|
14.8 Distribution Feeder Reclosing |
|
|
532 | (1) |
|
14.9 Subtransmission and Transmission-Line Reclosing |
|
|
533 | (2) |
|
14.10 Reclosing on Lines with Transformers or Reactors |
|
|
535 | (1) |
|
14.11 Automatic Synchronizing |
|
|
535 | (1) |
|
14.12 Frequency Relaying for Load Shedding–Load Saving |
|
|
535 | (2) |
|
14.13 Underfrequency Load-Shedding Design |
|
|
537 | (4) |
|
14.13.1 Underfrequency Load-Shedding Criteria |
|
|
537 | (1) |
|
14.13.2 Underfrequency Load-Shedding Scheme Architecture |
|
|
538 | (1) |
|
14.13.3 Underfrequency Control Scheme Design |
|
|
539 | (2) |
|
14.14 Performance of Underfrequency Load-Shedding Schemes |
|
|
541 | (1) |
|
14.15 Frequency Relaying for Industrial Systems |
|
|
541 | (1) |
|
|
542 | (1) |
|
14.17 Voltage Collapse Mitigating Techniques |
|
|
542 | (1) |
|
14.18 Protection and Control Trip Circuits |
|
|
543 | (1) |
|
14.19 Substation DC Systems |
|
|
544 | (1) |
|
14.20 Trip Circuit Devices |
|
|
545 | (3) |
|
|
545 | (1) |
|
14.20.2 Targeting and Seal-In Devices |
|
|
546 | (1) |
|
14.20.3 Switches and Diodes |
|
|
546 | (1) |
|
|
547 | (1) |
|
14.21 Trip Circuit Design |
|
|
548 | (1) |
|
14.22 Trip Circuit Monitoring and Alarms |
|
|
548 | (2) |
|
14.23 Special Protection Schemes |
|
|
550 | (1) |
|
14.24 Practical Considerations: Special Protection Schemes |
|
|
551 | (1) |
|
|
552 | (1) |
Chapter 15 Microprocessor Applications and Substation Automation |
|
553 | (28) |
|
|
553 | (1) |
|
15.2 Microprocessor-Based Relay Designs |
|
|
554 | (1) |
|
15.3 Programmable Logic Controllers |
|
|
555 | (1) |
|
15.4 Application of Microprocessor Relays |
|
|
555 | (1) |
|
15.5 Programming of Microprocessor Relaying |
|
|
556 | (7) |
|
|
556 | (6) |
|
15.5.2 Control Equation Elements |
|
|
562 | (1) |
|
|
562 | (1) |
|
|
562 | (1) |
|
|
562 | (1) |
|
|
562 | (1) |
|
15.6 Attributes of Microprocessor-Based Relays |
|
|
563 | (1) |
|
15.7 Protection Enhancements |
|
|
563 | (5) |
|
15.7.1 Distribution Protection Systems |
|
|
564 | (3) |
|
15.7.2 Transmission Protection Systems |
|
|
567 | (1) |
|
15.8 Multifunctional Capability |
|
|
568 | (1) |
|
15.9 Wiring Simplification |
|
|
569 | (1) |
|
|
569 | (2) |
|
15.10.1 Types of Event Reports |
|
|
570 | (1) |
|
15.11 Commissioning and Periodic Testing |
|
|
571 | (2) |
|
15.12 Setting Specifications and Documentation |
|
|
573 | (1) |
|
|
574 | (2) |
|
15.14 Power System Automation |
|
|
576 | (2) |
|
15.15 Practical Observations: Microprocessor Relay Application |
|
|
578 | (1) |
|
|
579 | (2) |
Chapter 16 Improving Protective System Performance |
|
581 | (38) |
|
16.1 Performance Measurement Techniques |
|
|
582 | (1) |
|
16.2 Measuring Protective System Performance |
|
|
583 | (1) |
|
16.3 Analyzing Protective System Misoperations |
|
|
583 | (3) |
|
16.3.1 Parameters for Measuring Protective System Performance |
|
|
584 | (1) |
|
|
585 | (1) |
|
16.4 NERC Standard PRC-004 |
|
|
586 | (1) |
|
16.5 Procedures for Implementing PRC-004 |
|
|
587 | (1) |
|
16.6 Tools for Analyzing Power System Events |
|
|
588 | (8) |
|
|
590 | (2) |
|
16.6.2 Dynamic Disturbance Recorders |
|
|
592 | (2) |
|
16.6.3 Sequence-of-Events Recorders |
|
|
594 | (2) |
|
16.7 Overview of Major Power Outages |
|
|
596 | (4) |
|
16.7.1 Northeast Blackout (November 9, 1965) |
|
|
596 | (1) |
|
16.7.2 West Coast Blackout (July 2, 1996) |
|
|
597 | (1) |
|
16.7.3 Northeast United States/Canadian Blackout (August 14, 2003) |
|
|
598 | (1) |
|
16.7.4 Florida Blackout (February 26, 2008) |
|
|
598 | (1) |
|
16.7.5 Pacific Southwest Outage (September 8, 2011) |
|
|
599 | (1) |
|
|
599 | (1) |
|
16.8 Relay Setting Loadability |
|
|
600 | (4) |
|
16.8.1 Three-Terminal Lines |
|
|
600 | (2) |
|
16.8.2 Remote Backup Protection |
|
|
602 | (2) |
|
16.9 NERC StandarcIPRC-023 |
|
|
604 | (6) |
|
16.9.1 Loadability of Distance Relays |
|
|
605 | (2) |
|
16.9.2 Requirements for Transformer Overload Settings |
|
|
607 | (1) |
|
16.9.3 Loadability of Pilot Schemes |
|
|
607 | (2) |
|
16.9.3.1 Loadability of DCB Pilot Schemes |
|
|
608 | (1) |
|
16.9.3.2 Loadability of POTT Pilot Schemes |
|
|
609 | (1) |
|
16.9.4 Switch-On-to-Fault Loadability |
|
|
609 | (1) |
|
16.10 Loadability Limits on Non-BES Lines |
|
|
610 | (2) |
|
16.11 Generator Trips during Disturbances |
|
|
612 | (1) |
|
16.12 Protection System Maintenance |
|
|
613 | (1) |
|
16.13 Grid Automation: Protection Aspects |
|
|
614 | (3) |
|
|
617 | (1) |
|
|
617 | (2) |
Chapter 17 Problems |
|
619 | (28) |
Index |
|
647 | |